| power solutions australia | ||
Redirecting to Selectronic... |
|
|
|
| ||
SGI Inverter Specifications |
||
Model |
SGI-3-110 |
SGI-4-110 |
SGI-5-110 |
SGI-6-110 |
|---|---|---|---|---|
|
Input voltages |
110 VDC |
110 VDC |
110 VDC |
110 VDC |
|
Operating DC voltage range |
98-168 |
98-168 |
98-168 |
98-168 |
|
Output voltage & frequency* |
240 Vac |
240 Vac |
240 Vac |
240 Vac |
|
MMPT working range |
105 - 155 VDC |
105 - 155 VDC |
105 - 155 VDC |
105 - 155 VDC |
|
Continuous output @ 40°C |
3 kW |
4 kW |
5 kW |
6 kW |
|
1 hour rating @ 40°C |
3.6 kW |
4.8 kW |
6 kW |
7.2 kW |
|
½ hour rating @ 40°C |
4 kW |
5.2 kW |
6.5 kW |
7.8 kW |
|
Peak efficiency |
> 94 % |
> 94 % |
> 94 % |
> 94 % |
|
Harmonic Distortion |
< 4% |
< 4% |
< 4% |
< 4% |
|
Off line losses |
< 10 W |
< 10 W |
< 15 W |
< 15 W |
|
Integrated isolation AC/DC |
cct breaker |
cct breaker |
cct breaker |
cct breaker |
|
Indicators |
LED & LCD |
LED & LCD |
LED & LCD |
LED & LCD |
|
Inverter mass |
60 kg |
65 kg |
70 kg |
72 kg |
|
Data logging |
RS232 |
RS232 |
RS232 |
RS232 |
Data Logging Remote Access: RS232 port, standard data logging and remote access via modem, satellite, GSM and CDMA technology.
Cooling: Convection and thermostatically controlled fans.
Enclosures: Electronics IP50, transformer and heatsink IP23. Weatherproof enclosures or rack mounting are available on request.
Protection: Over current trip, over voltage, over temperature, reverse polarity, fast electronic trip, transient over voltage protection.
All inverters are designed to AS3100 / AS2604 / AS61000.3.5 and the draft AS/NZ standard for grid connect inverters.
*AC output voltages of 110, 120, 220 and 230 are available on application.
Refer to sales staff for details of compliance.
Company Profile Product Range Contact Us
Questions or problems regarding this web site should be directed to admin@powersolution.com.au