| power solutions australia | ||
Redirecting to Selectronic... |
|
|
|
| ||
3 Phase SGB Inverter Specifications |
||
Model |
SGB-15-48 |
SGB-15-108
|
SGB-20-108
|
SGB-25-108
|
SGB-30-108
|
SGB-40-120 |
|---|---|---|---|---|---|---|
|
Input voltages |
48 VDC |
108 / 120 V |
108 / 120 V |
108 / 120 V |
108 / 120 V |
120 VDC |
|
Continuous output @ 40°C |
15 kW |
15 kW |
20 kW |
25 kW |
30 kW |
40 kW |
|
1 hour rating @ 40°C |
18 kW |
18 kW |
24 kW |
30 kW |
36 kW |
48 kW |
|
½ hour rating @ 40°C |
19.5 kW |
19.5 kW |
26 kW |
32.5 kW |
39 kW |
52 kW |
|
Surge rating |
30 kW |
30 kW |
40 kW |
50 kW |
60 kW |
80 kW |
|
Maximum change current |
250 A |
120 A |
150 A |
200 A |
250 A |
300 A |
|
Peak efficiency |
> 91 % |
> 93 % |
> 93 % |
> 93 % |
> 93 % |
> 93 % |
|
Power factor range |
0 - 1 |
0 - 1 |
0 - 1 |
0 - 1 |
0 - 1 |
0 - 1 |
|
Total Harmonic Distortion |
< 4% |
< 4% |
< 4% |
< 4% |
< 4% |
< 4% |
|
Idle power |
< 150 W |
< 150 W |
< 200 W |
< 250 W |
< 300 W |
400 W |
|
Integrated isolation AC/DC |
cct breaker |
cct breaker |
cct breaker |
cct breaker |
cct breaker |
cct breaker |
|
Indicators |
LED & LCD |
LED & LCD |
LED & LCD |
LED & LCD |
LED & LCD |
LED & LCD |
|
Inverter mass |
210 kg |
290 kg |
310 kg |
330 kg |
350 kg |
390 kg |
|
Internal DC contactor |
Yes |
Yes |
Yes |
No |
No |
No |
Automatic Bypass: Supply is maintained by the generator if the inverter is off line.
Operating DC voltage range: 92 % to 130 % of nominal.
Low distortion, high power load presented to generator during charging for best generator performance
Data Logging Remote Access: RS232 port, standard data logging and remote access via modem, satellite, GSM and CDMA technology.
All units are available with AC output voltages of 220 / 230 / 240 VAC, at 50 or 60 Hz (240 / 415, 230 / 380, three phase plus neutral connection), 120 / 208 VAC on application.
Cooling: Convection and thermostatically controlled fans.
Enclosures: Electronics IP50, transformer and heatsink IP23. Weatherproof enclosures or rack mounting are available on request.
Protection: Over current trip, over voltage, over temperature, reverse polarity, fast electronic trip, transient over voltage protection.
All inverters are designed to AS3100 / AS2604 / AS61000.3.5 and the draft AS/NZ standard for grid connect inverters.
Refer to sales staff for deails of compliance.
Company Profile Product Range Contact Us