power solutions australia

Home

Redirecting to Selectronic...
Click here if you are not redirected within 5 seconds.  


SGB Inverter Specifications

Model

SGB-10-108
SGB-10-120

SGB-12-108
SGB-12-120

SGB-15-120

Input voltages

108 / 120 VDC

108 / 120 VDC

120 VDC

Output voltage & frequency*

240 Vac
50 or 60 Hz

240 Vac
50 or 60 Hz

240 Vac
50 or 60 Hz

Continuous output @ 40°C

10 kW

12 kW

15 kW

1 hour rating @ 40°C

12 kW

14 kW

18 kW

½ hour rating @ 40°C

13 kW

15.6 kW

19.5 kW

Surge rating

22 kW

22 kW

30 kW

Maximum charge current

80 A

80 A

80 A

Harmonic distortion

< 4 %

< 4 %

< 4 %

Peak efficiency

> 94 %

> 94 %

> 94 %

Idle power

96 W

110 W

110 W

Standby

30 W

30 W

30 W

Autostart on demand

Yes

Yes

Yes

Mimimum start load

12 - 15 W

12 - 15 W

12 - 15 W

Integrated isolation AC/DC

cct breaker

cct breaker

cct breaker

Indicators

LED & LCD

LED & LCD

LED & LCD

Inverter mass

260 kg

260 kg

280 kg

Cooling system

5 fans

5 fans

5 fans

Data logging

Yes

Yes

Yes

Internal AC contactor

Yes

Yes

Yes

Remote access

RS232

RS232

RS232

Common to all units:

Standards:

All inverters are designed to AS3100 / AS2604 / AS61000.3.5 and the draft AS/NZ standard for grid connect inverters.

 

*AC output voltages of 110, 120, 220 and 230 are available on application.
* DC operating voltage range 92% to 130% of nominal.
Refer to sales staff for details of applicable compliance testing.

 