power solutions australia

Home

Redirecting to Selectronic...
Click here if you are not redirected within 5 seconds.  


RAPS Inverter Specifications

Model

RAP-3-24-1

RAP-3-48-1

RAP-5-48

RAP-5-110

RAP-5-120

Input voltages

24 VDC

48 VDC

48 VDC

110 VDC

120 VDC

Output voltage & frequency*

240 Vac
50 or 60 Hz

240 Vac
50 or 60 Hz

240 Vac
50 or 60 Hz

240 Vac
50 or 60 Hz

240 Vac
50 or 60 Hz

Continuous output @ 40°C

2.7 kW

3 kW

5 kW

5 kW

5 kW

1 hour rating @ 40°C

3.2 kW

3.6 kW

6 kW

6 kW

6 kW

½ hour rating @ 40°C

3.5 kW

3.9 kW

6.5 kW

6.5 kW

6.5 kW

Surge rating

5.4 kW

6 kW

10 kW

10 kW

10 kW

Maximum charge current

90 A

35 A

83 A

35 A

35 A

Peak efficiency

> 90 %

> 92 %

> 92 %

> 94 %

> 94 %

Power factor range

0 - 1

0 - 1

0 - 1

0 - 1

0 - 1

Idle power

35 W

35 W

50 W

50 W

50 W

Standby power

< 10 W

< 10 W

< 10 W

< 10 W

< 10 W

Integrated isolation AC/DC

cct breaker

cct breaker

cct breaker

cct breaker

cct breaker

Indicators

LED & LCD

LED & LCD

LED & LCD

LED & LCD

LED & LCD

Inverter mass

60 kg

60 kg

70 kg

70 kg

70 kg

Data logging

Yes

Yes

Yes

Yes

Yes

Internal Gen contactor

6 kVA

6 kVA

10 kVA

10 kVA

10 kVA

External Gen contactor

optional

optional

optional

optional

optional

Remote access

RS232

RS232

RS232

RS232

RS232

Common to all units:

Standards:

All inverters are designed to AS3100 / AS2604 / AS61000.3.5 and the draft AS/NZ standard for grid connect inverters.

 

*AC output voltages of 110, 120, 220 and 230 are available on application.
* Other DC voltages between 24 VDC and 120 VDC are available on application.

 

Company Profile Product Range Contact Us
Questions or problems regarding this web site should be directed to admin@powersolution.com.au