| power solutions australia | ||
Redirecting to Selectronic... |
|
|
|
| ||
RAPS Inverter Specifications |
||
Model |
RAP-3-24-1 |
RAP-3-48-1 |
RAP-5-48 |
RAP-5-110 |
RAP-5-120 |
|---|---|---|---|---|---|
|
Input voltages |
24 VDC |
48 VDC |
48 VDC |
110 VDC |
120 VDC |
|
Output voltage & frequency* |
240 Vac |
240 Vac |
240 Vac |
240 Vac |
240 Vac |
|
Continuous output @ 40°C |
2.7 kW |
3 kW |
5 kW |
5 kW |
5 kW |
|
1 hour rating @ 40°C |
3.2 kW |
3.6 kW |
6 kW |
6 kW |
6 kW |
|
½ hour rating @ 40°C |
3.5 kW |
3.9 kW |
6.5 kW |
6.5 kW |
6.5 kW |
|
Surge rating |
5.4 kW |
6 kW |
10 kW |
10 kW |
10 kW |
|
Maximum charge current |
90 A |
35 A |
83 A |
35 A |
35 A |
|
Peak efficiency |
> 90 % |
> 92 % |
> 92 % |
> 94 % |
> 94 % |
|
Power factor range |
0 - 1 |
0 - 1 |
0 - 1 |
0 - 1 |
0 - 1 |
|
Idle power |
35 W |
35 W |
50 W |
50 W |
50 W |
|
Standby power |
< 10 W |
< 10 W |
< 10 W |
< 10 W |
< 10 W |
|
Integrated isolation AC/DC |
cct breaker |
cct breaker |
cct breaker |
cct breaker |
cct breaker |
|
Indicators |
LED & LCD |
LED & LCD |
LED & LCD |
LED & LCD |
LED & LCD |
|
Inverter mass |
60 kg |
60 kg |
70 kg |
70 kg |
70 kg |
|
Data logging |
Yes |
Yes |
Yes |
Yes |
Yes |
|
Internal Gen contactor |
6 kVA |
6 kVA |
10 kVA |
10 kVA |
10 kVA |
|
External Gen contactor |
optional |
optional |
optional |
optional |
optional |
|
Remote access |
RS232 |
RS232 |
RS232 |
RS232 |
RS232 |
Automatic Bypass: Supply is maintained by the generator if the inverter is off line.
Low distortion, high power load presented to generator during charging for best generator performance.
Data Logging Remote Access: RS232 port, standard data logging and remote access via modem, satellite, GSM and CDMA technology.
Cooling: Convection and thermostatically controlled fans.
Enclosures: Electronics IP50, transformer and heatsink IP23. Weatherproof enclosures or rack mounting are available on request.
Protection: Over current trip, over voltage, over temperature, reverse polarity, fast electronic trip, transient over voltage protection.
All inverters are designed to AS3100 / AS2604 / AS61000.3.5 and the draft AS/NZ standard for grid connect inverters.
*AC output voltages of 110, 120, 220 and 230 are available on application.
* Other DC voltages between 24 VDC and 120 VDC are available on application.
Company Profile Product Range Contact Us