| power solutions australia | ||
Redirecting to Selectronic... |
|
|
|
| ||
3 Phase RAPS Inverter Specifications |
||
Model |
RAP-15-48 |
RAP-15-108
|
RAP-20-108
|
RAP-25-108
|
RAP-30-108
|
RAP-40-120 |
|---|---|---|---|---|---|---|
|
Input voltages |
48 VDC |
108/120 VDC |
108/120 VDC |
108/120 VDC |
108/120 VDC |
120 VDC |
|
Operating DC voltage range |
42-62 V |
100-158 V |
100-158 V |
100-158 V |
100-158 V |
100-158 V |
|
Continuous output @ 40°C |
15 kW |
15 kW |
20 kW |
25 kW |
30 kW |
40 kW |
|
1 hour rating @ 40°C |
18 kW |
18 kW |
24 kW |
30 kW |
36 kW |
48 kW |
|
½ hour rating @ 40°C |
19.5 kW |
19.5 kW |
26 kW |
32.5 kW |
39 kW |
52 kW |
|
Surge rating |
30 kW |
30 kW |
40 kW |
50 kW |
60 kW |
80 kW |
|
Maximum charge current |
250 A |
120 A |
150 A |
200 A |
250 A |
300 A |
|
Peak efficiency |
> 91 % |
> 93 % |
> 93 % |
> 93 % |
> 93 % |
> 93 % |
|
Power factor range |
0 - 1 |
0 - 1 |
0 - 1 |
0 - 1 |
0 - 1 |
0 - 1 |
|
Idle power |
< 150 W |
< 150 W |
< 200 W |
< 250 W |
< 300W |
< 400W |
|
Integrated isolation AC/DC |
cct breaker |
cct breaker |
cct breaker |
cct breaker |
cct breaker |
cct breaker |
|
Indicators |
LED & LCD |
LED & LCD |
LED & LCD |
LED & LCD |
LED & LCD |
LED & LCD |
|
Inverter mass |
210 kg |
290 kg |
310 kg |
330 kg |
350 kg |
390 kg |
|
Internal Gen contactor |
no |
< 30 kVA |
< 30 kVA |
no |
no |
no |
|
External Gen contactor |
required |
optional |
optional |
required |
required |
required |
Automatic Bypass: Supply is maintained by the generator if the inverter is off line.
Low distortion, high power load presented to generator during charging for best generator performance.
All units available in 220 / 230 / 240 VAC 50 or 60 Hz output (240 / 415, 230 / 380V three phase plus neutral connection). 120 / 208 VAC on application.
Data Logging Remote Access: RS232 port, standard data logging and remote access via modem, satellite, GSM and CDMA technology.
Cooling: Convection and thermostatically controlled fans.
Enclosures: Electronics IP50, transformer and heatsink IP23. Weatherproof enclosures or rack mounting are available on request.
Protection: Over current trip, over voltage, over temperature, reverse polarity, fast electronic trip, transient over voltage protection.
All inverters are designed to AS3100 / AS2604 / AS61000.3.5 and the draft AS/NZ standard for grid connect inverters.
Low distortion, high power presented to to generator during charging for best generator performance.
Refer to sales staff for details of applicable compliance testing.
Company Profile Product Range Contact Us
Questions or problems regarding this web site should be directed to admin@powersolution.com.au